This is the most common specification covering three grades of non-shrink grout:
Grade A Pre-Hardening Volume-Adjusting: Volume control of grout is caused by expansion before hardening occurs.
Grade B Post-Hardening Volume-Adjusting: Volume control of grout is caused by expension after grout hardens.
Grade C Combination Volume-Adjusting: Volue control of grout is caused by a combination of both mechanisms.
Compressive Strength
| 1 day | 1000 psi |
| 3 day | 2500 psi |
| 7 day | 3500 psi |
| 28 day | 5000 psi |
| Early Age Height Change | Grade A | Grade B | Grade C |
|---|---|---|---|
| Max % @ Final Set | +4.0% | N/A | +4.0% |
| Min % @ Final Set | 0.0% | N/A | 0.0% |
| Height Change of Moist Cured Grout @ , 3, 14, & 28 Days | Grade A1 | Grade B2 | Grade C |
|---|---|---|---|
| Max % @ Final Set | N/A | +0.3% | +0.3% |
| Min % @ Final Set | 0.0% | 0.0% | 0.0% |
1 If post-hardening expansion occurs during evaluation of a Grade A material, then the material shall be evaluated according to the Grade C criteria.
2 If pre-hardening expansion occurs during evaluation of a Grade B material, then the material shall be evaluated according to the Grade C criteria.